Moxa IOLOGIK E2212 Uživatelský manuál Strana 91

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 106
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 90
Click&Go User’s Manual Examples and Applications
4-23
I/O Mode Configuration
1. Configure the DIO channel to DO mode, set the alias name for each channel.
2. Configure the AI channel to 4-20 mA mode, set the alias name for each channel.
Programming Manners
1. Primary Pump and its indicator is activated when liquid level reaches High (15 mA input)
2. Backup Pump and its indicator is activated when the liquid level reaches High-high
(18 mA input), incase the primary pump is fail. High-high Alarm is triggered as well.
3. High-high Alarm is OFF when the liquid level goes back to High Level, both pumps keep
working
4. Primary Pump and its indicator is deactivated when the liquid level reaches Low (7 mA input)
5. Backup Pump and its indicator is deactivated when the liquid level reaches Low (7 mA input)
6. E-mail warning when reaching the High-high level
7. Remote control the primary/backup pump manually (Internal Register 0/1)
Click&Go Rule-set
Zobrazit stránku 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 105 106

Komentáře k této Příručce

Žádné komentáře